Encapsulant coatings shall be for specific use in ventilation systems and applied per manufacturer's instructions including safety instructions. Encapsulant coatings shall be applied directly to the interior porous surfaces of AC/ventilation system components by hand brushing, rolling, or troweling, or via spray system, with a maximum distance of 24" from the spray discharge tip to the surface being treated. Encapsulant coatings may not be fogged into the system. A continuous film thickness should be achieved in treated areas, as per manufacturer's instructions. Encapsulants shall be water-based, with low VOC (volatile organic compound) emissions, and meet NFPA smoke development and flame spread requirements for ventilation system products. Encapsulant coatings shall be applied in accordance with applicable federal, state, or local regulations regarding the use of such products and MSDS copies for any encapsu]ant products used in the AC/ventilation system shall be available on-site.

Areas of damaged interior AC/ventilation system fan unit or duct insulation that is abraded or delaminated such that application of an encapsulant coating would be inappropriate as determined by the NADCA-certified ASCS should be removed in consultation with building management. Replacement of such insulation with an appropriate material shall be the responsibility of building management.

Procedures

1. Identify the system to be cleaned including outside air intake, fan unit, supply ducts and return ducts if appropriate.

2. Determine how the system will be segregated for cleaning; typically the fan unit will be cleaned separately from the ductwork unless the ductwork consists of very short runs on the same floor. Cleaning should start from the furthest point in the system and proceed towards the collection device.

3. Lock out and tag out the fan unit. Building management will be responsible for identify and disabling in-duct smoke detectors if present.

4. Attach a local capture, HEPA filtered, Air Filtration Device (AFD) or vacuum collection system to place the system under negative pressure. Sufficient negative pressure shall be maintained to prevent the dispersion of dust outside of the duct. Isolation/zone pillows shall be used as necessary to isolate sections of the system, so that sufficient negative pressure is maintained in each work zone.

5. Exhaust the AFD or vacuum collection system to the outdoors. If no window is available, a stairwell may be appropriate. Alternately, two AFD's or vacuum collection systems may be connected in series so that a second unit filters the exhaust air from the first. Alternately, the cleaning contractor can have the collection equipment leak tested in-place by an independent third party to ensure that contaminants do not leak through the air cleaning device.

6. Cover all open supply air grilles, supply diffusers, and return air grilles located in the affected ductwork using fire-retardant polyethylene sheeting or bags and duct tape or preservation tape.

7. Place the air handling units and their components under containment prior to beginning work. A temporary Zip-wall containment of 6-mil, fire retardant polyethylene sheeting extending from the floor to the ceiling deck, with a flapped entrance, and maintained

NYC-WTC 000135783

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000135783Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000117345 · Box DEP Box 46

January 30, 2003 letter from Athenica Environmental Services regarding HVAC and environmental inspections at 250 South End Avenue.

Similar indexed content

Compare copies and versions →