WTC Indoor Dust Cleaning Program ACA^entilation System Cleaning Procedures General

1. It is necessary to ensure that sufficient air velocity and/or negative pressure is maintained in the duct during cleaning, to prevent the dispersion of dust outside of the duct. A HEPA filtered vacuum collection device shall be used to depressurize the ductwork to be cleaned. The AFD or vacuum collection equipment shall be adequate to collect all dust and debris released by the cleaning process and shall be attached to the existing ductwork with air-tight connections and located to attain maximum collection efficiency.

2. A temporary containment should be installed around the air handling units during cleaning to provide additional protection against the release of dust. Containment is not required for air handling units located outdoors unless located near active air intakes.

3. When cleaning the AC/ventilation system fan unit or other components, it is important that all components in contact with the air stream are cleaned. This procedure anticipates that once an air handling system has been selected for cleaning, all components, not just those with visible WTC dust, are cleaned.

4. Provisions must be made to prevent the release of dust or debris at access points that are disturbed by the cleaning activities. If the branch ducts are accessible (typically 6’ or less in length from access point) it is not necessary to construct a temporary containment at the access point provided that a) they may be cleaned using HEPA vacuums with brush attachments and wet methods and b) negative pressure within the system is sufficient to provide a face velocity at the diffuser or grille opening of 500 feet per minute. For longer branches that require the use of mechanical devices such as whips, brushes, and compressed air, or where it is not possible to establish a face velocity at the diffuser or grille opening of 500 feet per minute, construct a temporary containment (e.g., a “cube” or “cocoon” with flapped entrance) at the access point to provide protection against the release of dust.

5. It is recommended that air filtration devices and vacuum collection equipment be exhausted to the outdoors unless special measures are taken to control the leakage of air contaminants from the exhaust of such equipment (see Procedures item 7).

6. Note that porous interior duct insulation may be located in some of the AC/ventilation fan units or in ducts. Unless the insulation is protected by a metal screen, care must be taken to avoid damaging or tearing the insulation. For duct cleaning, soft rotary brushes, compressed air or HEPA vacuums may be used for cleaning. In AC/ventilation fan units, HEPA vacuums may be used for cleaning. After satisfactory cleaning of porous interior insulation, an appropriate encapsulant shall be applied to the porous surface.

Encapsulant coatings shall be for specific use in ventilation systems and applied per manufacturer's instructions including safety instructions. Encapsulant coatings shall be applied directly to the interior porous surfaces of AC/ventilation system components by hand brushing, rolling, or troweling, or via spray system, with a maximum distance of

NYC-WTC_000162747

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000162747Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →