24" from the spray discharge tip to the surface being treated. Encapsulant coatings may not be fogged into the system. A continuous film thickness should be achieved in treated areas, as per manufacturer's instructions. Encapsulants shall be water-based, with low VOC (volatile organic compound) emissions, and meet NFPA smoke development and flame spread requirements for ventilation system products. Encapsulant coatings shall be applied in accordance with applicable federal, state, or local regulations regarding the use of such products and MSDS copies for any encapsulant products used in the AC/ventilation system shall be available on-site.
Areas of damaged interior AC/ventilation system fan unit or duct insulation that is abraded or delaminated such that application of an encapsulant coating would be inappropriate as determined by the NADCA-certified ASCS should be removed in consultation with building management. Replacement of such insulation with an appropriate material shall be the responsibility of building management.
Procedures
1. Identify the system to be cleaned including outside air intake, fan unit, supply ducts and return ducts if appropriate.
2. Determine how the system will be segregated for cleaning; typically the fan unit will be cleaned separately from the ductwork unless the ductwork consists of very short runs on the same floor. Cleaning should start from the furthest point in the system and proceed towards the collection device.
3. Lock out and tag out the fan unit. Building management will be responsible for identify and disabling in-duct smoke detectors if present.
4. Attach a local capture, HEPA filtered. Air Filtration Device (AFD) or vacuum collection system to place the system under negative pressure. Sufficient negative pressure shall be maintained to prevent the dispersion of dust outside of the duct. Isolation/zone pillows shall be used as necessary to isolate sections of the system, so that sufficient negative pressure is maintained in each work zone.
5. Exhaust the AFD or vacuum collection system to the outdoors. If no window is available, a stairwell may be appropriate. Alternately, two AFD’s or vacuum collection systems may be connected in series so that a second unit filters the exhaust air fi-om the first. Alternately, the cleaning contractor can have the collection equipment leak tested in-place by an independent third party to ensure that contaminants do not leak through the air cleaning device.
6. Cover all open supply air grilles, supply diffusers, and return air grilles located in the affected ductwork using fire-retardant polyethylene sheeting or bags and duct tape or preservation tape.
7. Place the air handling units and their components under containment prior to beginning work. A temporary Zip-wall containment of 6-mil, fire retardant polyethylene sheeting extending from the floor to the ceiling deck, with a flapped entrance, and maintained under negative pressure using a HEPA-filtered air filtration device is sufficient. The footprint of the containment should be large enough to accommodate a ladder or scaffolding if needed.
NYC-WTC_000162748
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
6 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000162731
EPA submits detailed technical questions and comments on proposed HVAC cleaning procedures for WTC buildings.
5 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.960
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
NYC-WTC_000140014
Technical specifications for the application of encapsulant coatings on ventilation system components, including safety and material requirements.
1 shared non-person entities · 1 shared topics · similarity 0.953
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140013
Technical specifications for the application of encapsulant coatings on ventilation system components.
4 shared non-person entities · 1 shared topics · similarity 0.952
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140027
Technical guidance on maintaining air velocity and negative pressure during duct cleaning, HEPA device specifications, and dust containment methods.
3 shared non-person entities · 1 shared topics · similarity 0.950
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140026
Draft cleaning protocol specifying isolation techniques, vacuum collection methods, HEPA equipment use, and contamination control procedures for ventilation ducts.
4 shared non-person entities · 1 shared topics · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140511
Draft document outlining regulations and assistance programs for residential cleaning following the World Trade Center collapse.
4 shared non-person entities · 1 shared topics · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140517
Departmental comments and requests for clarification regarding cleaning triggers, clearance levels, and supervision requirements.
4 shared non-person entities · 1 shared topics · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140603
Contract establishing requirements for third-party asbestos monitoring and air sampling in residential buildings.
4 shared non-person entities · 1 shared topics · similarity 0.946
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000097177
Permit application requesting licensed asbestos contractors to clean debris and dust from the interior of 125 Cedar Street.
4 shared non-person entities · 1 shared topics · similarity 0.944
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000165014
Memo from EPA to multiple NYC, state, and federal agencies coordinating WTC environmental response activities and information sharing.
3 shared non-person entities · 1 shared topics · similarity 0.944
machine-extracted · confidence unavailable · Check page ↗More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000162712
Official notice instructing staff to preserve scanned World Trade Center documents as potential evidence in future legal actions.
Filed in the same folder
NYC-WTC_000162713
Official notice instructing staff not to dispose of original World Trade Center documents as they are required for legal proceedings.
Filed in the same folder
Filed in the same folder
NYC-WTC_000162729
DEP submits OSHA compliance justification document for review regarding worker safety in WTC cleanup procedures.
Filed in the same folder
NYC-WTC_000162731
EPA submits detailed technical questions and comments on proposed HVAC cleaning procedures for WTC buildings.
Filed in the same folder