Page2 Milford Management 10/17/01

CLEANING PROCEDURES FOR VERTICAL HVAC AND EXHAUST DUCTING

Step 1. Perform a thorough visual inspection to determine the accessibility to the system. Vertical shafts often pose many challenges for cleaning procedures and remote inspection devices may be used.

Step 2. A remote vacuum/collector device will be attached to the duct to collect the contaminants once they become dislodged inside the ducts.

Step 3. The vacuum/collector is connected to the lower most portion of the shaft allowing the forces of gravity to help pull the debris into the vacuum system.

Step 4. Additional access to the vertical shaft will be gained on each floor of the building by inserting the cleaning tools into the duct and working the debris toward the shaft and then down to the point of vacuum hook up.

Step 5. At the time of the cleaning of a particular floor's duct work, it is imperative that the outlet and register openings of all other floors in the line be sealed off to prevent contamination from coming out of the system. Moreover, this helps in maintaining the negative air pressure within the system and improves the dust collection capability of our vacuum system. We will work with your staff in order to schedule accessibility to all units within a line in order that we service at least one line per day.

Step 6. Each grill or register is manually cleaned and degreased prior to reinstallation.

Any damage or conditions that affect the proper functioning of the system will Be reported to the building representative and management.

NYC-WTC 000120682

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000120682Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

No available related records indexed in this group.

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000131089 · Box DEP Box 53

Letter from NYLS Director enclosing ambient air sampling data for post-9/11 environmental assessment.

Cited alongside this record in an Ask answer

NYC-WTC_000095044 · Box DEP Box 02

Cover letter enclosing air sampling and asbestos bulk sampling reports for American Stock Exchange properties dated February 2002.

Cited alongside this record in an Ask answer

NYC-WTC_000102890 · Box DEP Box 36

Cover letter enclosing ambient air sampling results from post-September 11, 2001 for the New York Law School facility.

Cited alongside this record in an Ask answer

Compare copies and versions →