October 22, 2001
Mr.Elliot Zuckerman
Cushman & Wakefield
a/a/f Mercantile Exchange
One North End Avenue
New York, New York 10282
Re: One North End Avenue
Ambient Project #211338
Dear Mr. Zuckermen:
The following is a su}nmart' of the
performed on Sdp`te ibex 16t indoor environmental quality survey that Amvey benti Group,
n, 2001 at the above referenced location.
sampling for airborne metals, carbon dioxide, The ncluded
humidity, polynuclear aromatic carbon monoxide, temperature,
hydrocarbons and airborne asbestos relative
structures by TEM.
Analysis of all indoor readings for
indoor readings were below OSHA,carbon dioxide and carbon monoxide revealed that all
guidelines and/or regulations, ACGI} , ASHRAE and other
recommended industry
The indoor temperature readings
readings ranged from 53,4% to ranged from 66.0°? to 69, indoor
with the conditions described in60.7%. Al! indoor relative humidity readingrelative ity
the ASHRAE 55-1992 thermal were consistden
ideal indoor conditions. ' The comfort standard as well as
indoor remp re gs We slightly below the ASHRAE
55-1992 thermal standard for fall/winter
(69°Fin76
month
Four (4) TEM samples were
collected from floors 3, 7, 11 and
by transmission electron from the lobby and analyzed
microscopy (TEM) for asbestos
analysis indicated that airborne structures. The results of the
testing were less than the an asbestos levels inside and outside the
alytical building at the time of
standard of 70 Structures/mm2 as sensitivity of the instrument, which is well below the EPA
well as other recommended
regulations. industry guidelines and/or
Four (4) air samples were
collected from floors 3, 7, 11 and
polynuclear aromatic hydrocarbons in from the lobby and analyzed for
that the levels of the air. Analysis of all four
individual compounds were below the (4) samples collected revealed
Limits and NIOSH REi, guidelines. OSHA Permissible Exposure