October 22, 2001
Mr, Elliot Zuckerman
Cushman & Wakefield
a/a/f Mercantile Exchange
One North End Avenue
New York, New York 10282
Re: One North End Avenue
Ambient Project # 211338
Dear Mr. Zuckernien:
The following is a summary of
the
Inc. Performed on September Igs indoor environmental quality survey Group,
', 2001 at the above referenced llocati
sampling for airborne metals, on. TheAssu, y included
carbon dioxide, carbon monoxide,
humidity, polynuclear aromatic temperature, relative
hydrocarbons and airborne asbestos
structures by TEM.
Analysis of all indoor readings for
carbon dioxide and carbon
indoor readings were below OSHA, monoxide revealed that all
ACGIH, ASHRAE and other
guidelines and/or regulations_ recommended industry
The indoor temperature readings
ranged from 67.9"F' to 71.3°F. The
readings ranged from 31.2% to 38,8%, indoor relative humidity
All indoor relative humidity
with the conditions described readings were consistent
in the ASHRAE 55-1992 thermal
ideal indoor conditions. One comfort standard as well as
indoor temperature reading
55-1992 thermal standard for slightly below the ASI~I2AE
fall/winter months (69°F - 76°F).
Four (4) air samples were
collected from various locations
analyzed by transmission electron on floors 2, 3, 7 and l5 and
the analysis indicated that microscopy (TEM) for asbestos
airborne asbestos levels inside and structures. The results of
of testing were less than the outside the building at the time
analytical sensitivity of the
EPA standard of 70 instrument,
structures/mm2 as well as other recommended which is well below the
regulations. industry guidelines and/or