SECTION 02082
approved by NYCDEP and the City, worker decontamination facilities shall be attached
to the Work Areas
a) Structure:
(1) Use modular systems or build using wood or metal frame studs, joists, and
rafters placed at a maximum of 16 inches on-center.
(2) When worker decontamination unit is located outdoors, in areas with
public access, or in correctional facilities, frame work shall be lined with
minimum 3/8” thickness plywood sheathing. Sheathing shall be caulked or
taped airtight at all joints and seams.
(3) Interior shall be covered with two layers of opaque 6-mil polyethylene
sheeting, with a minimum overlap of 16 inches at seams. Seal seams
airtight using tape and adhesive. The interior floor shall be covered with
two (2) layers of reinforced fire-retardant polyethylene sheeting with a
minimum overlap on the walls of sixteen inches.
(4) Entrances to the decontamination unit shall be secured with lockable
hinged doors. Doors shall be open at all times when abatement operations
are in progress. Doors shall be louvered to allow for air movement through
the decontamination units into Work Area.
b) Curtained Doorways: A device to allow ingress or egress from one room to
another while permitting minimal air movement between the rooms.
c) Air Locks: Air locks shall consist of two curtained doorways placed a minimum
of three feet apart.
d) Decontamination Enclosure System shall be placed adjacent to the Work Area
and shall consist of three totally enclosed chambers, separated from Work Area
and each other by airlocks, as follows:
(1) Washroom: An equipment washroom shall have two air locks (one
separating the unit from the Work Area and one common air lock that
separates it from the holding area. The washroom shall have facilities for
washing material containers and equipment. Gross removal of dust and
debris from contaminated material containers and equipment shall be
accomplished in the Work Area, prior to moving to the washroom.
(2) Holding Area: A holding area shall share a common air lock with the
equipment washroom and shall have a curtained doorway to outside areas.
A hinged, lockable door shall be placed at the holding area entrance to
prevent unauthorized access into the Work Area.
B. Decontamination Enclosure System Utilities: Lighting, heat, and electricity shall be provided as
necessary by the Contractor, and as specified herein.
3.03 Personnel Entrance and Decontaminatioii Procedures for Removal Operations utilizing Remote
02082-64