=> Filtration after the heating/cooling coil - Tertiary Filtration Tertiary Filtration in the supply ductwork. Filtration after the heating/cooling coil -

The most important quality of an efficient filtration system is to properly treat the outside and return air before it is introduced into the conditioned space. Outside air fresh air is ideally treated to be free of all dust, gases, and contaminants that would adversely affect the building’s occupants.

Return air typically contains particulate matter that was generated within the space in addition to particulate matter that was not removed by the supply air filtration system.

The number of filtration systems was based on the practical locations based on existing system configurations and the ability of the existing HVAC systems to be modified to accommodate the increased system static due to additional filtration systems.

Outside Air Filtration

To adequately filter the school’s outside air it was decided to add additional 2” wide filter racks for all systems. Typically this was accomplished by adding new filter racks immediately before or after the existing outside air dampers. Alternate locations were provided in the HVAC systems mixed air section where inadequate space existed to add filter racks as described above.

The filter chosen for filtering the outside air was a carbon-activated filter that would effectively filter total volatile organic compounds (TVOC’s) filtration.

The characteristics of the carbon activated pre-filter is as follows:

Return Air Filtration

To provide additional filtration of supply air, the existing 2” wide filter racks on the majority of the HVAC central air handlers were utilized. Baseline air balance testing also indicated that, for a majority of the HVAC systems, it was not mechanical feasible to increase filtration beyond the static pressure drop caused by the combination of the 2” wide pre-filter and the additional 2” wide after filter.

The filter chosen for the after filter was a 4 ply pleated filter having a MERV rating of 9- 11 and an AHSRAE 52.2 efficiency of 30-40%.

The characteristics of the 4 ply after pleated after-filter is as follows:

DOE00048139.DOC Appendix 1 - Page 14

CITY_21MC100_011284785

NYC-WTC_000453561

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000453561Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →