Asbestos Abatement

passing this inspection shall be recorded in a daily logbook.

(4) The Testing Laboratory will conduct a visual observation of the Work Area to verify the absence of asbestos-containing waste materials.

(5) If the Work is accepted by the Testing Laboratory based on the inspection, Contractor shall be notified. Conduct the following activities in accordance with the contract and all applicable laws, codes, rules and regulations.

(a) All waste shall be removed from the Work Area and holding areas.

(b) All tools and equipment are to be removed and decontaminated in the decontamination enclosure system.

(6) If the Work is not approved, the Testing Laboratory will inform Contractor who will then HEPA-vacuum and/or wet­ clean the Work Area. The Testing Laboratory will then perform a subsequent visual observation. This process will continue until the Testing Laboratory accepts the Work Area as clean.

(7) The Work Area shall be vacated for a minimum of one hour to allow fibers to settle prior to clearance air monitoring, when required.

(t) Final Barrier Removal

(1) Upon receipt of acceptable clearance testing results polyethylene sheeting (inside layers) and Isolation Barriers shall be removed and disposed accordingly as ACM.

(2) The area surrounding the abatement work place shall be cleaned of any visible debris utilizing HEPA-vacuum and wet methods.

(u) The Testing Laboratory will conduct final visual. Approval must be granted prior to break down of decontamination facility and contractor demobilization. Other Information: Extra time required to clean Work Areas in order to achieve clearance criteria shall not be considered grounds for an extension of time for contract completion.

CAPITAL PROJECT NUMBER PO79201K 02081-71 100: CONTRACT DOCUMENTS REV. May 3,2000 -71 -100% CONTRACT DOCUMENTS REV. 0: DATE

CITY_21MC100_006631320

NYC-WTC_000416832

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000416832Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Asbestos sampling chain of custody form

NYC-WTC_000233286

Chain of custody form for asbestos samples referencing New York State Department of Labor regulations and sample tracking details.

Similar indexed content

Asbestos, NY DOL reference

NYC-WTC_000441450

Asbestos standards reference page from NY Department of Labor materials.

Similar indexed content

Compare copies and versions →