Mr. Bernard P. Orlan January 31,2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATC Project No. 15-19125-0279
Respirable Particulates (PM2 ^)
Respirable particulate concentrations* indoors ranged between 18p,g/m3 to 40 ug/n^ All
measurements were within the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2 5
concentration for the entire school building was approximately 29 pg/m^. This average
concentration was below the USEPA recommended concentration for sensitive individuals such
as asthmatic people and children. The outdoor respirable particulate concentration ranged from
20'to 41 pg/m^ with an average of 33 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentratim
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Measurements of respirable particulates , CO2, CO and TVOCs were within applicable
standards and guidelines. All of the relative humidity measurements were also within the
ASHRAE recommended range of 30 to 60 percent for occupant comfort.
2. Thirty - three (33) temperature measurements were below the range of 68 to 75° F (at 50
percent relative humidity) recommended by ASHRAE Standard 55-1992.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 or 212.
Sincerely,
A TC ASSOCIA TES INC.
Reviewed by:
'^Yiannis Efstathiou James R. Cohn, CIH, CSP
Project Manager Regional Manager
Industrial Hygiene Division
CONFIDENTIAL, CITY_21MC100_001897942
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000410278