NYC 9/11 Public Portal Document

01/31/2002 11:07 FAX 212 353 8306 ATC ®005

Mr. Bernard P. Orlan January 30, 2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATC Project No. 15-19125-0297

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged from 30 jig/tn^ to 60 pg/m^ (A.M.) and 7 ,ug/m3 to 17 jAg/m^ (P,M.). All indoor measurements were below the NPAAQS of 65 ug/mS 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 44 ug/m^ (A.M.) and 12 gg/m^ (P.M.). The P.M. average concentration was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration averaged 73 pg/m^ (A.M.) and 25 ttg/m^ (P.M.).

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected (0.0 ppm) anywhere inside or outside the building.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was partially occupied at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1, Concentrations of CO2, CO and TVOCs were within applicable guidelines; 2. Eighteen (1S) measurements of temperature were above the recommended range; 3, All indoor measurements of relative humidity were within the recommended range; 4. Instantaneous readings of PM2,5 concentrations averaged below the NPAAQS of 65 pg/m^ but some A.M. readings were above the recommended level of 40 pg/m^.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353'8280, extension 261 or 212.

Sincerely, ATCASSOCIAT£S

James R. Cohn, CIH, CSP Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC100_009253009

NYC-WTC_000359619

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359619Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →