NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 5 pages

Indoor air quality memo, PS 89M

Machine-extracted title · confidence 44%

ATC memo re: IAQ report for PS 89M, Warren Street.

NYC-WTC_000359637–000359641
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

01/29/2002 11:42 FAX 212 353 8306 ATC @005

Mr. Bernard P. Orlan January 29,2002 Indoor Air Quality Assessment Page 4 P- S. 89M ATC Protect No. 15-19125-0297

Respirable Particulates (PM2,s)

Respirable particulate concentrations* indoors ranged from 21 gg/m^ to 85 pg/m^ (A.M.) and 12 M-g/m^ to 23 pg/m^ (P.M.). Ail indoor measurements, except one, were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 42 ug/m^. This average concentration was slightly above tlie USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration averaged 91 pg/m3 (A.M.) and 28 (Tg/mJ (P.M.),

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

7VOC Concentration

TVOCs were not detected (0.0 ppm) anywhere inside or outside the building.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; * No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented;

1. Concentrations of CO2, CO and TVOCs were within applicable guidelines; 2, Seventy of seventy-four measurements of temperature were within the recommended range; 3. Sixty-three of seventy-four indoor measurements of relative humidity were within the recommended range; 4. Instantaneous readings of PM2.5 concentrations averaged below the NPAAQS of 65 pg/m^ but above the recommended level of 40 gg/m^.

CITY_21MC100_012157789

NYC-WTC_000359640

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000359640Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ memo, PS 89M, Jan 2002

NYC-WTC_000400632

Report of indoor air quality measurements at PS 89M; January 28, 2002.