Mr. Bernard P. Orlan February' 5, 2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATC Project No. 15-19125-0297

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged from 18 pg/m^ to 35 pg/m^ (A.M.) and 9 pg/m3 to 22 pg/m3 (P.M.). All indoor measurements were below the NRAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration* for the entire school bu:lding was approximately 27 pg in- (A.M.) and 15 pg m-" (P.M.). All A.M. and P. M. indoor measurements were also below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration averaged 50 pg/m3 (A.M.) and 28 pg/m3 (P.M.).

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected (0.0 ppm) anywhere inside or outside the building.

OBSERVATIONS

During this assessment, ATC noted the following:

• The interior of the building appeared clean and free of dust and debris; • The school was partially occupied (I.S. 89) at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Respirable particulate, CO2, CO and TVOC concentrations were within applicable guidelines; 2. All but five (5) measurements of temperature were within the recommended range; 3. All indoor measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort.

CONFIDENTIAL, CITY_21MC100_003471855 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000245445

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000245445Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ memo, PS 89M, Jan 2002

NYC-WTC_000400632

Report of indoor air quality measurements at PS 89M; January 28, 2002.

Similar indexed content

Compare copies and versions →