Mr. Bernard P. Orlan February' 5, 2002 Indoor Air Quality Assessment Page 3 P. S. 89M ATC Project No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of eight (8 ) outdoors and thirty-two (32) inside in the morning (A.M.) and thirty-two (22) inside and eight (8) outside in the afternoon (P.M.). All five floors of the school were surveyed. The field data sheets are found in the Attachment. Readings began at 8:00 A.M. and concluded after 3:30 P.M. The results are described below:

Temperature

Indoor dry bulb temperature measurements ranged from 66.8°F to 73.2°F (A.M.) and 67.4°F to 72.9°F (PM). Five (5) measurements were below the rar ge of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These were readings on the 1st ,2“^^ and 3rd floors. The average outdoor temperature was 53.6°F (A.M.) and 48.3°F (P.M.).

Relative Humidity

The relative humidity indoors ranged from 17.3 to 28.0 percent (A.M.) and 16.2 to 27.9 percent (P.M.). All readings were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity averaged 21.9 percent (A.M.) and 20.6 percent (P.M.).

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 500 to 1109 ppm (A.M.) and 470 to 719 ppm (P.M.). All CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the backgj'ound level. The outdoor (background) CO2 concentrations averaged 502 ppm (A.M.) and 488 ppm (P.M.). Therefore, the maximum acceptable level of CO2 at this location was 1202 ppm (background level + 700 ppm). The highest indoor level was measured in Classroom 402. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primaiy' source of CO2 indoors is occupant respiration. The 2”^^ and 3’’^ floors of the school building were not occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the ASHRAE guideline of 9 ppm. The outdoor CO concenfration was also 0 ppm.

CONFIDENTIAL, CITY_21MC100_003471854 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000245444

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000245444Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ memo, PS 89M, Jan 2002

NYC-WTC_000400632

Report of indoor air quality measurements at PS 89M; January 28, 2002.

Similar indexed content

Compare copies and versions →