Indoor air quality report, P.S. 89M

Machine-extracted title · confidence 58%

IAQ measurements at P.S. 89M for re-occupancy planning.

NYC-WTC_000404294–000404298
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan Februaiy' 5, 2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATC Project No. 15-19125-0297

Respirable Particulates (PM2.5)

Respirable particulate concentrations* indoors ranged from 18 pg/m^ to 35 pg/m^ (A.M.) and 9 pg/m3 to 22 pg/m^ (P.M.). All indoor measurements were below the NPAAQS of 65 gg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration* for the entire school building was approximately 27 pg/m^ (A.M.) and 15 pg/m^ (P.M.). All A.M. and P. M. indoor measurements were also below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration averaged 50 pg/m3 (A.M.) and 28 pg/m^ (P.M.).

* The measurements made during this assessment were instantaneous readings, the NPA.A.QS is a 24-hour average.

TPOC Concentration

TVOCs were not detected (0.0 ppm) anywhere inside or outside the building.

OBSERVATIONS

During this assessment, ATC noted the following;

• The interior of the building appeared clean and free of dust and debris; • The school was partially occupied (I.S. 89) at the time of the assessment; • No smoke odor was detected in the building.

Based on the real-time measurements, the following findings are presented:

1, Respirable particulate, CO2, CO and TVOC concentrations were within applicable guidelines; 2. All but five (5) measurements of temperature were within the recommended range; 3. All indoor measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort.

NYC-WTC_000404297 CITY_21MC100_000491520

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000404297Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

IAQ report for PS 89M, Apr 2002 · Box unavailable

NYC-WTC_000220651

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.

12 shared non-person entities · 1 shared topics · similarity 0.997

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →