Mr. Bernard P. Orlan January 31,2002 Indoor Air Quality Assessment Page 4 P. S. 89M ATC Project No. 15-19125-0297

Respirable Particulates ('PM2,3)

Respirable particulate concentrations* indoors ranged from 13 pg/m^ to 23 pg/m^ (A.M.) and 16 pg/m3 to 29 pg/m^ (P.M.). All indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 18 pg/m^ (A.M.) and 21 pg/m^ (P.M.). All indoor measurements were also below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration averaged 29 pg/m3 (A.M.) and 38 pg/m^ (P.M.).

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

PyOC Concentration

TVOCs were not detected (0.0 ppm) anywhere inside or outside the building.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was partially occupied at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO2, CO and TVOCs were within applicable guidelines; 2. Two (2) afternoon measurements of temperature were below the recommended range; 3. Four (4) morning indoor measurements of relative humidity were below the recommended range; 4. Instantaneous readings of PM2.5 concentrations averaged below the NPAAQS of 65 pg/m^ and the recommended level of 40 pg/m^ for sensitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 261 or 212.

Sincerely, Reviewed by: A TCASSOCIA TES INC.

Andreas C. Andreou James R. Cohn, CIH, CSP Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC100_000490659 NYC-WTC_000400671

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000400671Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →