NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan January 23, 2002
Indoor Air Quality Assessment Page 4
P. S.234M ATC Project No. 15-19125-0279
particulate matter 2.5 micrometers or less in aerodynamic diameter as well as the USEPA
recommended respirable particulates concentration of 40 pg/nP for sensitive individuals such as
asthmatic people and children. The average PM2,5 concentration for the entire school building
was approximately 16 pg/m-’. The outdoor respirable particulate concentration ranged from 16 -
29 pg/mJ with an average of 21pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC CmcentrciCion
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration wa.s also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The ] st floor appeared to be dusty, especially the cafeteria and the general office;
• The building was not occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
I. Concentrations of respirable particulates, CO2, CO and TVOCs were within applicable
standards and guidelines;
2. All indoor measurements of relative humidity were within the ASHRAE-recommended
range of 30 to 60 percent for occupant comfort.
3. Forty-three (43) temperature measurements were below and one (1) measurement was above
the range of 68 to 75O F (at 50 percent relative humidity) recommended by ASHRAE
Standard 55-1992 during the heating season (wintertime conditions).
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 01-212.
Sincerely,
A TC ASSOCIA TES INC.
Reviewed by:
Andreas C. Andreou James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager
Industrial Hygiene Division
CONFIDENTIAL, CITY_21MC100_003444665
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000249449
OCR can misread numbers and units. Confirm readings against the page image before using them.