11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗Indoor air quality report, PS 234M, Jan 2002
Machine-extracted title · confidence 95%Cover letter and report detailing indoor air quality measurements collected at PS 234M on January 24, 2002, to evaluate building contamination.
NYC-WTC_000177847–000177851
OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan January 25, 2002 Indoor Air Quality Assessment Page 4 P. S. 234M ATCProiectNoJ5-19125-02^
concentration for the entire school building was approximately 44 pg/m^. This average concentration was slightly above the USEPA recommended concentration for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentration ranged from 36 - 60 pg/m^ with an average of 51pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOQC(U2cenlrati^
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: • The 1 floor appeared to be dusty, especially the cafeteria and the general office; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • This particular day it was rainy and it was also very humid.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of respirable particulates, CO2, CO and TVOCs were within applicable standards and guidelines; 2. Three indoor measurements of relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. 3. Forty (40) temperature measurements were below the range of 68 to 75° F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 261 or 212.
Sincerely, A TC ASSOCIA TES INC. Reviewed by:
Andreas C. Andreou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division
CONFIDENTIAL, CITY_21MC100_003444687
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000177850
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177990
Letter reporting indoor air quality measurements collected at P.S. 150M on May 28, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177942
Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.
11 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000185967
Report from ATC Associates detailing indoor air quality measurements collected at PS 89M for the Board of Education.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content