Indoor air quality report, PS 234M, Jan 2002

Machine-extracted title · confidence 58%

ATC IAQ measurements collected at PS 234M in January 2002.

NYC-WTC_000249446–000249450
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P, Orlan •lanuary 23, 2002 Indoor .Air Quality Assessment Page 3 P, S. 234M ATC Project No. 15-19125-0279

Real-Time Environmental Measurements

ATC collected fifty (50) sets of real-time environmental measurements consisting of fourty­ seven (47) from inside the school building and three (3) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 11 ;30 A.M. and concluded after 2:15 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 60.6 °F to 75.1 °F. Forty-three (43) measurements were below and one measurement was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements at the playground ranged from 49.1 to 50.3 °F.

Relative Humidity

The relative humidity indoors ranged from 15.5 percent to 22.6 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 13.0 to 17.8 percent.

Carbon Dioxide Conceutra/ion

Carbon dioxide concentrations indoors ranged from 460 ppm to 599 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations ranged 450 to 480 ppm. Therefore, the maximum acceptable level of CCb at this location was 1180 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school building during ATC's assessment was not occupied.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.

Respirable Farticulates CPAdy, 5)

Respirable particulate concentrations* indoors ranged between 9 pg/m^ to 29 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of

CONFIDENTIAL, CITY_21MC100_003444664 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000249448

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000249448Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

IAQ report for PS 89M, Apr 2002 · Box unavailable

NYC-WTC_000220651

Formal indoor air quality assessment report submitted to the Board of Education regarding measurements taken at PS 89M on April 17, 2002.

11 shared non-person entities · 1 shared topics · similarity 0.995

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, PS 234M, Jan 2002

NYC-WTC_000177847

Cover letter and report detailing indoor air quality measurements collected at PS 234M on January 24, 2002, to evaluate building contamination.

Similar indexed content

Compare copies and versions →