NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality report, P.S. 89M, Jan 2002

Machine-extracted title · confidence 35%

ATC Associates reports IAQ measurements conducted at the referenced school for the NYC BOE.

NYC-WTC_000245343–000245346
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orian January 24, 2002 Indoor Air Quality Assessment Page 3 P. S. 89 (Manhattan) ATC Project No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy- six (76) from inside the school building and four (4) outdoors from the playground. All five floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 2:30 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 68.0 °F to 76.0 °F. Two (2) measurements were above the range of 68 to 75"F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions ). The outdoor temperature measurements at the playground ranged from 49.1 to 52.0 °F.

Relative Humidity

The relative humidity indoors ranged from 18.2 percent to 40.8 percent. Twenty (20) measurements were within the ASPfRAE-recommended range of 30 to 60 percent for occupant comfort. All other measurements were below the recommended range. The outdoor relative humidity ranged from 25.0 to 36.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 480 ppm to 1150 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations ranged 458 to 475 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1175 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school building during ATC’s assessment was not occupied.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.

Respirable Particulates iPM2Jj

Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 17 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter as well as the USEPA

CONFIDENTIAL, CITY_21MC100_003471742 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000245345

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000245345Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →