Mr. Bernard P. Orian January 24, 2002 Indoor Air Quality Assessment Page 3 P. S. 89 (Manhattan) ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected eighty (80) sets of real-time environmental measurements consisting of seventy- six (76) from inside the school building and four (4) outdoors from the playground. All five floors of the school were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 2:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.0 °F to 76.0 °F. Two (2) measurements were above the range of 68 to 75"F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions ). The outdoor temperature measurements at the playground ranged from 49.1 to 52.0 °F.
Relative Humidity
The relative humidity indoors ranged from 18.2 percent to 40.8 percent. Twenty (20) measurements were within the ASPfRAE-recommended range of 30 to 60 percent for occupant comfort. All other measurements were below the recommended range. The outdoor relative humidity ranged from 25.0 to 36.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 480 ppm to 1150 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations ranged 458 to 475 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1175 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school building during ATC’s assessment was not occupied.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.
Respirable Particulates iPM2Jj
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 17 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter as well as the USEPA
CONFIDENTIAL, CITY_21MC100_003471742 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000245345
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000384033
ATC report of IAQ measurements collected January 23, 2002 at PS 89M for NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400594
Report of indoor air quality measurements at PS 89M for BOE project.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000226873
ATC Associates report on indoor air quality measurements collected at P.S. 89M on January 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383993
ATC IAQ measurements collected January 17–18, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249454
Indoor air quality measurements collected January 23, 2002 at PS 234M.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245331
ATC Associates provides IAQ measurement results for P.S. 89M requested by NYC BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245303
IAQ measurements at P.S. 89M; January 18, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000314815
IAQ measurements collected March 19, 2002 at PS 234M for BOE.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396289
ATC IAQ measurements at PS 234M, January 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000392852
ATC IAQ report for May 14, 2002 measurements at PS 89M for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000397291
IAQ measurements at PS 234M; BOE requested assessment of air quality.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177954
Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000384033
ATC report of IAQ measurements collected January 23, 2002 at PS 89M for NYC BOE.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400594
Report of indoor air quality measurements at PS 89M for BOE project.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000226873
ATC Associates report on indoor air quality measurements collected at P.S. 89M on January 17, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400582
Report of IAQ measurements at PS 89M, NYC BOE building, January 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400563
IAQ report for January 18, 2002, at PS 89M with multiple measurements.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000245296
IAQ measurements at P.S. 89M; January 16, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000384033
ATC report of IAQ measurements collected January 23, 2002 at PS 89M for NYC BOE.
Similar indexed content
NYC-WTC_000400594
Report of indoor air quality measurements at PS 89M for BOE project.
Similar indexed content
NYC-WTC_000226873
ATC Associates report on indoor air quality measurements collected at P.S. 89M on January 17, 2002.
Similar indexed content
NYC-WTC_000383993
ATC IAQ measurements collected January 17–18, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000249454
Indoor air quality measurements collected January 23, 2002 at PS 234M.
Similar indexed content