Mr. Bernard P. Orlan January 31, 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50) from inside the school building and ten (10) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found ih Attachment 1. Readings began at 11:00 P.M. and concluded after 3:00 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 58.9 °F to 69.9 °F. Thirty - three (33) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 40.1 to 47.3 °F.

Relative Humidity

The relative humidity indoors ranged from 32.0 percent ,to 42.7 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 39.8 to 51.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 579 ppm to 1190 ppm. All CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations ranged 420 to 525 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1225 ppm (background level 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school building was not occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1 to 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations also ranged from 0 to 1 ppm.

CONFIDENTIAL, CITY_2IMCl0 0_0 01897941 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008 NYC-WTC_000410277

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000410277Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Indoor air quality report, PS 234M, Jan 2002

NYC-WTC_000177847

Cover letter and report detailing indoor air quality measurements collected at PS 234M on January 24, 2002, to evaluate building contamination.

Similar indexed content

Compare copies and versions →