Mr. Bernard P. Orlan January 31, 2002
Indoor Air Quality Assessment Page 3
P. S. 234M ATC Project No. 15-19125-0279
Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50)
from inside the school building and ten (10) outdoors. All three floors of the school were
surveyed. These results are described below.
Field data sheets are found ih Attachment 1. Readings began at 11:00 P.M. and concluded after
3:00 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 58.9 °F to 69.9 °F. Thirty - three (33)
measurements were below the range of 68 to 75°F (at 50 percent relative humidity) as
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
The outdoor temperature measurements ranged from 40.1 to 47.3 °F.
Relative Humidity
The relative humidity indoors ranged from 32.0 percent ,to 42.7 percent. All of the
measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort. The outdoor relative humidity ranged from 39.8 to 51.3 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 579 ppm to 1190 ppm. All CO2
measurements were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations ranged 420 to 525 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1225 ppm (background level 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school
building was not occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 to 0 ppm for all readings. These
concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO
concentrations also ranged from 0 to 1 ppm.