NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, Feb 2002, High School for Leadership

Machine-extracted title · confidence 44%

Indoor air quality measurements report dated Feb 5, 2002 for the referenced school.

NYC-WTC_000297663–000297666
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P Orlan February 6, 2002 Indoor Air Quality Assessment Page 3 H S for Leadership & Pub Service (M894) ATCProiectNo 15-19125-0290

Real-Time Environmental Measurements

ATC collected one hundred and thirty-nme (139) sets of real-time environmental measurements consisting of one hundred and thirty-three (133) in the school building and six (6) outdoors All fourteen floors of the school were surveyed Field data sheets are found in the Attachment Readings began at 8’00 A M and concluded after 3 20 P M The results are described below

Temperature

Indoor dry bulb temperature measurements ranged from 63 8°F to 73 8°F Thirty (32) of the measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions) These measurements were collected on the 1st, 5th , gth ,9th iQth , 11th , 12th , 13th and 14th floors The outdoor temperature range was 35 1°F to 40.4°F

Relative Humidity

The relative humidity indoors ranged from 17.6 percent to 33.1 percent All but three of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 17.6 and 33.1 percent

CarbonDioxideCgtwentration

Carbon dioxide concentrations indoors ranged from 415 ppm to 1282 ppm Three (3) of the measurements were above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level The outdoor (background) CO2 concentrations ranged from 412 ppm to 511 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1211 ppm. (background level -1- 700 ppm). The highest reading was recorded in Room 1105, occupied by 27 people Levels above the recommended maximum do not indicate a health nsk. Carbon dioxide measurements are used as an indicator of available outdoor air. The pnmary source of CO2 indoors is occupant respiration

CarbonMonoxide Concentration

Carbon monoxide concentrations indoors were 0-2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 0-2 ppm

Respirable Particulates (PM2 5/

Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 34 pg/ None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter The average outdoor respirable particulate concentrations ranged from 34 pg/m^ to 59 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC100_003087951

NYC-WTC_000297665

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000297665Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ report, Feb 12, 2002, ATC

NYC-WTC_000297722

Indoor air quality report for Feb 12, 2002 at the school, with monitoring details.

Similar indexed content

NYC-WTC_000297790

ATC IAQ report for Feb 13, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000297826

ATC report of IAQ measurements collected Feb 15, 2002 at the referenced school.

Similar indexed content

Compare copies and versions →