Mr Bernard P Orlan February 15, 2002 Indoor Air Quality Assessment Page 3 H S for Leadership & Pub Service ('M894) ATCProiectNo 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and thirty-four (134) in the school building and six (6) outdoors All fourteen floors of the school were surveyed Field data sheets are found in the Attachment Readings began at 8 35 A M and concluded after 3 15PM The results are described below
Tempef-g/ure
Indoor dry bulb temperature measurements ranged from 58 2°F to 74 3°F Fourteen (14) of the measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions) The outdoor temperature range was 37 1°F to 45 7°F
Relative Humidity
The relative humidity indoors ranged from 18 3 percent to 35 9 percent One hundred and twenty-eight (128) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort The outdoor relative humidity range was 37 1 to 45 7 percent
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 526 ppm to 1289 ppm Thirteen (13) of the measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level The outdoor (background) CO? concentrations ranged from 412 ppm to 471 ppm Therefore, the maximum acceptable level of CO2 at this location was 1171 ppm (background level + 700 ppm) The highest reading was recorded in Room 905, occupied by 23 people at around 1 55 PM Levels above the recommended maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator of available outdoor air The primary source of CO2 indoors is occupant respiration
Carbon Monoxide ConcenHodi^
Carbon monoxide concentrations indoors were 1-2 ppm These concentrations were below the NPA.A.QS/ASHRAE guideline of 9 ppm The outdoor CO concentrations were 0-4 ppm
Respirable Particulates (PM2 j)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 38 pg/m^ with an average 13 pg/m^ None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2 5 micrometers or less m aerodynamic diameter The outdoor respirable particulate concentrations ranged from 28 pg/m^ to 61 pg/m^ with an average of 46 pg/m^
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average
CITY_21MC100_003088063
NYC-WTC_000297810
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000297790
ATC IAQ report for Feb 13, 2002 at the referenced school.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297681
Indoor air quality report for the school, Feb 6, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297826
ATC report of IAQ measurements collected Feb 15, 2002 at the referenced school.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297663
Indoor air quality measurements report dated Feb 5, 2002 for the referenced school.
11 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297757
ATC quality report for IAQ measurements at a NYC high school in Feb 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256872
ATC report on indoor air quality measurements at a NYC high school site, conducted Feb 7, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297686
Report of IAQ measurements collected Feb 8, 2002 at the referenced New York City school.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297874
ATC report of IAQ measurements collected on Feb 28, 2002 at the referenced school.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297704
Indoor air quality report for Feb 11, 2002 at the referenced school.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189753
Cover letter and report summary for indoor air quality measurements collected at a school on February 27, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297722
Indoor air quality report for Feb 12, 2002 at the school, with monitoring details.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000257035
IV notes on IAQ measurements collected for BOE program, Feb 2002.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000297790
ATC IAQ report for Feb 13, 2002 at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000189753
Cover letter and report summary for indoor air quality measurements collected at a school on February 27, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000256872
ATC report on indoor air quality measurements at a NYC high school site, conducted Feb 7, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295895
March 2002 IAQ measurements at a NYCBOE school to assess air quality maintenance.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295811
ATC report of IAQ measurements at NYC school; March 11, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000297722
Indoor air quality report for Feb 12, 2002 at the school, with monitoring details.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC IAQ report for Feb 13, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000297681
Indoor air quality report for the school, Feb 6, 2002.
Similar indexed content
ATC report of IAQ measurements collected Feb 15, 2002 at the referenced school.
Similar indexed content
Indoor air quality measurements report dated Feb 5, 2002 for the referenced school.
Similar indexed content
ATC quality report for IAQ measurements at a NYC high school in Feb 2002.
Similar indexed content