Real-Time Environmental Measurements
ATC collected one hundred and forty-one (141) sets of real-time environmental measurements
consisting of one hundred and thirty-six (136) in the school building and five (5) outdoors All
fourteen floors of the school were surveyed Field data sheets are found in the Attachment
Readings began at 8 17 AM and concluded after 1 43 P M The results are described below
Temperature
Indoor dry bulb temperature measurements ranged from 66 8°F to 74 9°F Ten (10) were below
the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard
55-1992 during the heating season (wintertime conditions) The outdoor temperature range was
41 7°F to 54.5°F
Relative Humidity
The relative humidity indoors ranged from 29 percent to 30 8 percent 24 readings were below
the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity range was 28 6 to 40 percent
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 375 ppm to 1064 ppm None of the
measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level The outdoor (background) CO2
concentrations ranged from 332 ppm to 599 ppm Therefore, the maximum acceptable level of
CQ2 at this location was 1108 ppm (background level + 700 ppm). The highest reading was
recorded in Room 515 at around 1 03 P.M Levels above the recommended maximum do not
indicate a health risk Carbon dioxide measurements are used as an indicator of available
outdoor air The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1-2 ppm These concentrations were below the
NPAAQS/ASHRAE guideline of 9 ppm The outdoor CO concentrations were 2-4 ppm
Respirable Particulates (PM2 5)
Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 37 pg/m^ with an
average 9 pg/m^ None of the measurements were above the NPAAQS of 65 pg/m3 24-hour
average concentration of particulate matter 2.5 micrometers or less m aerodynamic diameter.
The outdoor respirable particulate concentrations ranged from 51 pg/m^ to 95 pg/m^ with an
average of 66 ug/m^
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average