Mr. Bernard P. Orlan -April 10, 2002 Indoor Air Quality Assessment Pages H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 10:45 A.M. and concluded after 1:50 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 70.3 °F to 77.5 “F. One hundred and ten (110) indoor measurements for temperature were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 68.5 °F to 73.4 °F.
Re!ali\’e /■fumidiiy
The relative humidity indoors ranged from 42.2 percent to 52.9 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 40.9 to 49.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 419 ppm to 1410 ppm. Two (2) the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 422 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1122 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 2 ppm- 4 ppm.
Respirable Particulates (PM2_s)
Respirable particulate concentrations* indoors ranged between 2 gg/m^ to 36 pg/m^ with an average 6 pg/m^- All of the indoor measurements for PM2,5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 36 pg/m^ to 54 pg/m^ with an average of 43 pg/m^. Six (6) of the twelve (12) instantaneous outdoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.
CITY_21MC100_003086562
NYC-WTC_000189399
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180220
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182899
Report of indoor air quality measurements collected at PS 234M on February 25, 2002, to determine if acceptable air quality is maintained.
10 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Similar indexed content
Similar indexed content
Similar indexed content
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in May 2002.
Similar indexed content