Mr Bernard P Orlan February 28, 2002 Indoor Air Quality Assessment Page 2 H S. for Leadership & Pub Service (M894') ATCProiectNo 15-19125-0290 The assessment was performed consistent with generally accepted indoor air quality assessment practices As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, vanations in indoor air quality parameters and sampling and analytical accuracy

The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities

EVALUATION CRITERIA

Currently, there are no regulatory standards for indoor air quality in non-mdustrial buildings, such as offices and schools For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications

Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE), Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992), Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA)

Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times

TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

targetl

Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2 5) of air (p,g/m3) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer. 73-79°F at 50% RH ASHRAE 55 Wmter- 68-75°F at 50% RH Relative Humidity 30-60% ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association

CITY_21MC100_006797806

NYC-WTC_000189754

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000189754Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000180220

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in May 2002.

Similar indexed content

Compare copies and versions →