NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, Feb 12, 2002, ATC

Machine-extracted title · confidence 44%

Indoor air quality report for Feb 12, 2002 at the school, with monitoring details.

NYC-WTC_000297722–000297725
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr Bernard P. Orlan February 13, 2002 Indoor Air Quality Assessment Page 3 H.S for Leadership & Pub. Service (M894) ATCProiectNo 15-19125-0290

Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and thirty-four (134) m the school building and six (6) outdoors All fourteen floors of the school were surveyed Field data sheets are found m the Attachment Readings began at 8 00 A M and concluded after 2'40 P M The results are described below

Temperature

Indoor dry bulb temperature measurements ranged from 65 9°F to 75.2°F. Four (4) of the measurements were below and one (1) measurement was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 dunng the heating season (wintertime conditions) The outdoor temperature range was 40 4°F to 47 8°F.

Relative Humidity

The relative humidity indoors ranged &om 19 1 percent to 44.6 percent. One hundred and thirty (130) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 21.1 to 28,4 percent

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 441 ppm to 1246 ppm. Four (4) of the measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level The outdoor (background) CO2 concentrations ranged from 403 ppm to 432 ppm Therefore, the maximum acceptable level of CO2 at this location was 1132 ppm (background level + 700 ppm) The highest reading was recorded in Room B06, occupied by 22 people at around 2:40 P,M, Levels above the recommended maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator of available outdoor air. The pnmary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 -2 ppm.

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 21 pg/m^ with an average 5 pg/m^- None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less m aerodynamic diameter. The outdoor respirable particulate concentrations ranged from 12 pg/m^ to 47 pg/m^ with an average of 31 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average

CITY_21MC1OO_OO6797712 NYC-WTC_000297724

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000297724Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000297663

Indoor air quality measurements report dated Feb 5, 2002 for the referenced school.

Similar indexed content

NYC-WTC_000297790

ATC IAQ report for Feb 13, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000297775

ATC IAQ report for Feb 26, 2002 at the referenced NYC school.

Similar indexed content

Compare copies and versions →