filtration devices (AFDs) used during cleaning. All horizontal surfaces were wet wiped.
This cleaning method was used for each cleaning event.
Numeric Criteria - This unit met the numeric criteria listed in Table 1 for each compound
after being cleaned twice.
Asbestos
Before cleaning samples - Pre-cleaning micro vacuum and wipe samples were collected for
asbestos. These samples indicate that asbestos was present prior in the unit before cleaning.
All three of the micro vacuum samples detected chrysotile, and four of the five wipe samples
detected chrysotile. The remaining sample was below the detection limit.
Post J" Cleaning Samples - Post-cleaning micro vacuum, wipe and air samples were
collected for asbestos. All three of the air samples, which were analyzed using PCM, TEM
AHERA, and TEM PCMe, could not be analyzed due to overloading of particulate material.
Due to this situation, a second cleaning was conducted.
The results of the three micro vacuum samples indicate that asbestos was present at levels
lower than those observed before cleaning, with one of the samples being identified as below
the detection limit.
The results of the five wipe samples indicate that asbestos was present in all of the samples,
but generally at lower concentrations than those observed before cleaning.
Post 2^ Cleaning Samples - Four post-cleaning air samples were collected for asbestos.
These samples were analyzed using PCM, TEM AHERA, and TEM PCMe. The results for
the PCM analysis were below the secondary numeric criterion of 0.01 f/cc, with one sample
being below the detection limit. The TEM AHERA results were all below the detection
limit. THE TEM PCMe results were also all below the primary numeric criterion of 0.0009
s/cc. This indicates that the cleaning techniques were effective at reducing the particulate
matter, which allowed valid air samples to be collected and analyzed.
Dioxin
Before Cleaning Samples - There were four pre-cleaning wipe samples collected and
analyzed for dioxin. The results indicate that there was dioxin present; however, the TEQ
concentrations for each sample were below the numeric criterion of 4 ng/m^.
Post J" Cleaning Samples - There were four post-cleaning wipe samples collected and
analyzed for dioxin. The results indicate that there was dioxin present; however, the TEQ
concentrations for each sample were below the numeric criterion of 4 ng/m^ and detected at
lower concentrations than the pre-cleaning samples. This indicates that the cleaning
techniques were effective in reducing dioxin concentrations.
51
CITY_21MC100_004205007
NYC-WTC_000276703