Gypsum
Before Cleaning Samples - There were four pre-cleaning wipe samples collected. The results
indicate gypsum was not detected above the detection limit range of 5 to 20 mg/m^.
Post P' Cleaning Samples - There were two air samples and four wipe samples collected after
the first cleaning. The results indicate that gypsum was not detected above the detection limit
of 0.008 mg/in ’ for the air samples, and not detected above the detection limit of 10 mg/m^
for wipe samples.
Lead
Before Cleaning Samples - There were three micro vacuum samples and four wipe samples
collected. One of the three micro vacuum samples was above the comparison value. The
other two results were below the detection limit. The results indicate lead was detected in
two of the four wipe samples at concentrations above the primary numeric criteria of 25
pg/ftL The micro vacuum sample exceeded the comparison value at 50.7 pg/ft^ and the two
wipe samples exceeded the primary numeric criteria at 112 pg/ft^ and 201 pg/ftf
Post P' Cleaning Samples - There were two air samples, three micro vacuum samples, and
four wipe samples collected after the first cleaning. The two air samples were below the
numeric criteria but were qualified as rejected due to field blank contamination. The results
of the micro vacuum and wipe samples show that, while one of the micro vacuum (qualified
as rejected) and two of the wipes samples exceeded the detection limits, all samples met the
comparison value and primary numeric criterion for lead after the first cleaning. Therefore,
additional samples were not collected.
Alpha Quartz
Before Cleaning Samples - There were four pre-cleaning wipe samples collected. Two of the
four samples were below the detection limit and the other two samples had alpha-quartz
detected.
Post Cleaning Samples - There were two air and four wipe samples collected after the first
cleaning. All samples were below the detection limit except one wipe sample; however,
there is not an established criterion for alpha-quartz in settled dust.
Calcite
Before Cleaning Samples - There were four pre-cleaning wipe samples collected. All foui-
samples were below the detection limit.
Post P' Cleaning Samples - There were two air samples and four wipe samples collected
after the first cleaning. All of the samples were below the detection limit. Since all of the
samples were below the detection limits after the first cleaning, no additional samples were
collected for calcite.