Bulk sample analysis report, NYC-DCAS, 60 Manhattan

Machine-extracted title · confidence 42%

Laboratory analysis of bulk samples for NYC-DCAS at 60 Manhattan building address.

NYC-WTC_000266372–000266383
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

KAMUINbUUANIS 35-40 36tb Street Long Island City NewYork.ttlOO Tel: (718)729-1997 Fax: 718)729-1876

BULK SAMPLE A VALYSIS REPORT CLIENT: NYC-DCAS BUILDING ADDRESS: 60 Centre Street, Manhattan, N'^ PROJECT#: Client Sample ID# 11 12 13 14 15 Lab Sample ID# 010919B-1132 010919B-1133 010919B-1134 010919B-1135 010919B-H36

Sample Location. 7th Floor 7th Floor 7th Floor 7th Floor 5th Floor Conference Rm Meeh Room 2 Meeh. Room 2 Meeh. Room 2 Bathroom by Vent Exhaust Inside Duct of Inside Duct of Inside Duct of Stair 5H West Wall MC-AHU-7-15 MC-AHU-7-14 Supply Air Window Sill Homogeneity Yes Yes Yes Yes Yes

Sample Description Dust Dust Dust Dust Dust Wipe W ipe W ipe ipe Wipe

Color BIk BIk BIk BIk BIk

Texture. Mixed Mixed Mixed Mixed Mixed

Sample Treatment None None None None None

Asbestos Present; (Type & Percent) ND ND ND ND ND Total Percent Asbestos: 0% 0% 0% 0% 0% Other Fibr. Mat. (Type & Percent): 3%SYNTH 5%SYNTH 10%SYNTH 8%SYNTH IO%SYNTH 2%CELL 3%CELL Non Fibr. Mat. (Percent): 95% 95% 90% 92% 87% Date Received. 9/19/01 Date of Analysis 9/19/01 Date of Report; 9/19/01

Analyst: Lab Manager: Roody Lou. David Chen * Analysis of samples is performed by Ppl<rized Light Microscopy (PLM) - Point Counting Method (EPA 600/M4-82-020) * Analytical equipments: Stereobinocular microscope (MEIJI EMT-Serial # 25930), Polarized Light Microscope (MEIJI ML-POL-Serial # 88034) * PLM is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated a; non-asbestos-containing * Samples will be stored for ninety (90) davs and then returned to the client upon request * The results relate only to the items calibrated or tested. * The certificate of report shall not be reproduced without thn written approval of the laboratory * The report must not be used by the client to claim endorsement by NVLAP or any agency of the US Government NYS-DOH ELAP # 11273 MST-N^LAP ft 102047 AIHAtf: 100269

3

CITY_21MC100_002777726

NYC-WTC_000266374

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000266374Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →