Mr. Bernard P. Orlan May 9, 2002 Indooi Air Quality Assessment Page 3 H.S. o f Economics and Finance (M833)________ ATC Project No. 15-19125-0291 REAL Time Environmental Measurements
ATC ( ollected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indooi dry bulb temperature measurements ranged from 73.2 °F to 84.0 °F. Seventy-four (74) of the indoor measurements collected were above and fourteen (14) measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature measurements ranged from 69.2 °F to 73.8 °7.
Relative Humidity
The relative humidity indoors ranged from 31.8 percent to 53.1 percent. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity' ranged from 31.7 to 49.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 489 ppm to 1375 ppm. Two (2) of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 ‘.'oncentration was 482 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1182 ppm (background level + 700 ppm). The highest reading (1375 ppm) was measured in room # 305 around 2:48 P.M. with 18 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 to 1 ppm. These concentrations were belov’ the NPyVAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 to 2 ppm.
Respirable Particulates (PM2j)
Resp:rable particulate concentrations* indoors ranged between 3 pg/m^ to 37 ug ni ' with an average of 12 pg/m^- All of the indoor measurements for respirable particulates were below the NPA\QS of 65 pg/m-’ 24-hour average concentration of particulate matter 2.5 micrometers or less n aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 22 pg/m^ to 96 p.g/m3 with an average of 54 pg/m^-
CONFIDENTIAL, CITY_2IMCl00_003462509 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259374
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259184
ATC Associates report on IAQ measurements taken April 12, 2002 at the school for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180089
Report of indoor air quality measurements collected at the referenced school on June 14, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259358
Indoor air quality measurements collected May 7, 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259330
Indoor air measurements collected May 3, 2002 for the BOE IAQ program.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259344
ATC indoor air quality measurements conducted May 6, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180015
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 9, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259425
Indoor air measurements collected May 20, 2002 for BOE IAQ program.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259539
ATC indoor air quality measurements at the High School of Economics and Finance, June 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259515
ATC IAQ measurements report for June 13, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259495
ATC IAQ measurements report for June 5, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259507
ATC IAQ measurements report for June 11, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180019
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 10, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000180089
Report of indoor air quality measurements collected at the referenced school on June 14, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259330
Indoor air measurements collected May 3, 2002 for the BOE IAQ program.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259358
Indoor air quality measurements collected May 7, 2002 for BOE program.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259184
ATC Associates report on IAQ measurements taken April 12, 2002 at the school for BOE review.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259149
ATC IAQ measurements collected March 25, 2002 for BOE program.
Similarity score 0.982 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180015
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 9, 2002.
Similarity score 0.981 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC Associates report on IAQ measurements taken April 12, 2002 at the school for BOE review.
Similar indexed content
NYC-WTC_000180089
Report of indoor air quality measurements collected at the referenced school on June 14, 2002.
Similar indexed content
Indoor air quality measurements collected May 7, 2002 for BOE program.
Similar indexed content
Indoor air measurements collected May 3, 2002 for the BOE IAQ program.
Similar indexed content
ATC indoor air quality measurements conducted May 6, 2002 for BOE.
Similar indexed content