Mr. Bernard P. Orlan April 15, 2002 Indoo! Air Quality Assessment Page 3 H.S. of Economics and Finance (MS33) AFC Proiect No. 15-19125-0291
Real -Time Environmental Measurements
ATC collected thirty-nine (39) sets of real-time environmental measurements consisting of thirty-five (35) in the school building and four (4) outdoors. Field data sheets are found in the Attachment. Readings began at 11.’45 A.M. and concluded after 1:21 P.M. The results are descriaed below.
Temperature
Indoo■ dry bulb temperature measurements ranged from 58.2 °F to 77.8 °F. Four (4) of the indoor measurements for temperature were above, and four (4) measurements were bellow and twenp/'Cight (28) measurements were within the range of 68 to 75°F (at 50 percent relative humic ity) recemmended by ASHRAE Standard 55-1992 during the heating season (wintertime condhions). The outdoor temperature ranged from 52.2 to 58.9 °F.
Rdab ye HumidUy
The relative humidity indoors ranged from 27.8 percent to 39.0 percent. Three (3) of the indoor measurements for relative humidity were below and thirty-two (32) were within the ASHRAE recorr mended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 31.0 to 33.0 percent.
Carben Dioxide Concentration
Carben dioxide concentrations indoors ranged from 385 ppm to 1021 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximurr. concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 422 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1142 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoo' air. Tne primary source of CO2 indoors is occupant respiration.
Carb jn ATonoxide Concentration
Carbon monoxide concentrations indoors were between 1 to 3 ppm. These concentrations were below the NPAAQS/ASEIRAE guideline of 9 ppm. The outdoor CO concentration ranged from 2 ppm to 3 ppm.
Resp rable Particulates (PM2 5)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 42 ug/m^ with an aven ge 13 pg/m^- None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and one (1) Indoor Measurement was above the USEPA recommended concentration of 40 pg/m-^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 16 pg/m^ to 42 pg/m^ with an average of 31 pg/m-\ None of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of parti eulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the four (4)
CONFIDENTIAL, CITY_21MC100_003462244 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259186
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259358
Indoor air quality measurements collected May 7, 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180089
Report of indoor air quality measurements collected at the referenced school on June 14, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259372
Indoor air measurements collected May 8, 2002 for BOE IAQ program.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259330
Indoor air measurements collected May 3, 2002 for the BOE IAQ program.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259425
Indoor air measurements collected May 20, 2002 for BOE IAQ program.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259200
Indoor air quality measurements taken April 18, 2002 for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259539
ATC indoor air quality measurements at the High School of Economics and Finance, June 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259344
ATC indoor air quality measurements conducted May 6, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259149
ATC IAQ measurements collected March 25, 2002 for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259547
ATC indoor air quality measurements at the referenced school, June 26, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259145
Report of IAQ measurements at 100 Trinity Place for BOE program, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383084
IAQ measurements collected on April 12, 2002 for BOE evaluation at the school.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000180089
Report of indoor air quality measurements collected at the referenced school on June 14, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259358
Indoor air quality measurements collected May 7, 2002 for BOE program.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259425
Indoor air measurements collected May 20, 2002 for BOE IAQ program.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259372
Indoor air measurements collected May 8, 2002 for BOE IAQ program.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259330
Indoor air measurements collected May 3, 2002 for the BOE IAQ program.
Similarity score 0.987 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000294353
Report of IAQ measurements at P.S. 234M, requested by NYC BOE, dated March 1, 2002.
Similarity score 0.986 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality measurements collected May 7, 2002 for BOE program.
Similar indexed content
NYC-WTC_000180089
Report of indoor air quality measurements collected at the referenced school on June 14, 2002.
Similar indexed content
Indoor air measurements collected May 8, 2002 for BOE IAQ program.
Similar indexed content
Indoor air measurements collected May 3, 2002 for the BOE IAQ program.
Similar indexed content
Indoor air measurements collected May 20, 2002 for BOE IAQ program.
Similar indexed content