Mr. Bernard P. Ori an May 6, 2002 Indoo- Air Quality Assessment Page 3 H.S. cf Economics and Finance tM833)________ ATC Project No. 15-19125-0291 Real -T [me Environ m ental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are descriaed below.
Tempiratiire
Indoor dry bulb temperature measurements ranged from 69.5 °F to 76.2 °F. All the indoor measurements collected were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor tempe'ature measurements ranged from 62.0 °F to 68.5 °F.
Relqti-^e Humidity
The relative humidity indoors ranged from 19.2 percent to 29.2 percent. All the indoor measurements for relative humidity were bellow the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 18.1 to 20.8 percent.
Carbon Dioxid? Concentration
Carbon dioxide concentrations indoors ranged from 386 ppm to 1496 ppm. Three (3) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maxirrum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 472 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1172 ppm (background level + 700 ppm). The highest reading (1496 ppm) was measwed in room # 410 around 3:05 PM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primar/ source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors was 0 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm
Respirable Pariiculates (PM2,3)
Respirable particulate concentrations* indoors ranged between 0 pg/m^ to 51 pg/m^ with an average 7 pg/m^- One (1) of the indoor measurements for respirable particulates was above the NPAAQS of 6:5 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less ii aerod:/namic diameter. One (1) of the eighty-eight (88) indoor instantaneous measu'ements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 19 pg/m^ to 56 pg/m^ w:th an average of 40 pg/m^. All outdoor measurements for respirable particulates were v ithin the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Seven (7) outdoor instantaneous measurements
CONFIDENTIAL, CITY_21MC100_003462464 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259332
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259425
Indoor air measurements collected May 20, 2002 for BOE IAQ program.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259358
Indoor air quality measurements collected May 7, 2002 for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180015
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 9, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396436
May 3, 2002 IAQ measurements for BOE at HSEF (M833).
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259515
ATC IAQ measurements report for June 13, 2002 at the school.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259184
ATC Associates report on IAQ measurements taken April 12, 2002 at the school for BOE review.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259507
ATC IAQ measurements report for June 11, 2002 at the school.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259495
ATC IAQ measurements report for June 5, 2002 at the school.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259149
ATC IAQ measurements collected March 25, 2002 for BOE program.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259286
May 1, 2002 IAQ measurements for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259204
ATC report of IAQ measurements collected April 19, 2002 for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259344
ATC indoor air quality measurements conducted May 6, 2002 for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259358
Indoor air quality measurements collected May 7, 2002 for BOE program.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259372
Indoor air measurements collected May 8, 2002 for BOE IAQ program.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180089
Report of indoor air quality measurements collected at the referenced school on June 14, 2002.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180015
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 9, 2002.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385111
ATC IAQ measurements collected June 17, 2002 for BOE at the High School of Economics and Finance.
Similarity score 0.987 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259184
ATC Associates report on IAQ measurements taken April 12, 2002 at the school for BOE review.
Similarity score 0.987 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air measurements collected May 20, 2002 for BOE IAQ program.
Similar indexed content
Indoor air quality measurements collected May 7, 2002 for BOE program.
Similar indexed content
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 9, 2002.
Similar indexed content
May 3, 2002 IAQ measurements for BOE at HSEF (M833).
Similar indexed content
ATC IAQ measurements report for June 13, 2002 at the school.
Similar indexed content