IAQ field report, High School of Economics and Finance, May

Machine-extracted title · confidence 33%

Indoor air measurements collected May 3, 2002 for the BOE IAQ program.

NYC-WTC_000259330–000259333
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P, Orlan May 6, 2002 Indoor Air Quality Assessment Page 4 H.S. (if Economics and Finance (M833) ATC Project No. 15-19125-0291 were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC ConcenfraCion

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC conce itration was also 0.0 ppm.

OBSI.RVATIQNS

During this assessment, ATC noted the following: • Tlie interior of the building appeared clean and free of dust and debris; • Tlie building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Indoor concentrations of CO and TVOCs were below applicable standards and guidelines. 2. All the indoor measurements collected were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. 3. All the indoor measurements for relative humidity were bellow the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 4. fl rec (3) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 472 ppm. Therefore, the maximum acceptable lev'el of CO2 at this location was 1172 ppm (background level -+- 700 ppm). The highest reading (1496 ppm) was measured in room # 410 around 3:05 PM. 5. One (1) of the eighty-eight (88) indoor instantaneous measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. Seven (7) outdo(ir instantaneous measurements were above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals and children.

It IS our pleasure to provide these indoor air quality services to the New York City Board of Educacion. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, /I TCASSOCIA TES INC. Re^wed by:

Hrasnd'boddapaneni Tames R. Cohii CIH, C^ Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CONFIDENTIAL, CITY_21MC100_003462465 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259333

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259333Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259425

Indoor air measurements collected May 20, 2002 for BOE IAQ program.

Similar indexed content

NYC-WTC_000259358

Indoor air quality measurements collected May 7, 2002 for BOE program.

Similar indexed content

NYC-WTC_000180015

Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 9, 2002.

Similar indexed content

NYC-WTC_000396436

May 3, 2002 IAQ measurements for BOE at HSEF (M833).

Similar indexed content

NYC-WTC_000259515

ATC IAQ measurements report for June 13, 2002 at the school.

Similar indexed content

Compare copies and versions →