Mr. Bernard P. Orlan March 13, 2002
Indoor Air Quality Assessment Page 4
H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291
of the twelve (12) instantaneous outdoor readings were above the USEPA recommended
concentration of 40 for sensitive individuals / children.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0,0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and fi-ee of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below applicable standards and guidelines.
2. Concentrations of relative humidity were within the applicable standards and guidelines.
3. Thirty-four (34) of the indoor measurements for temperature were below and forty-nine (49)
were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by
ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
4. Seven (7) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
highest reading (1482 ppm) was measured in Room # 705 approximately at 4:29 PM with 21
occupants. Levels above the recommended maximum do not indicate a health risk. Carbon
dioxide measurements are used as an indicator of available outdoor air. The primary source
of CO2 indoors is occupant respiration.
5. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour
average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.
Two (2) of the eight-eight (88) instantaneous indoor readings were above the USEPA
recommended concentration of 40 |xg/m3 for sensitive individuals / children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
336 or 212.
Sincerely,
TOASSOCIA TES INC. Reviewed by: ----- i
AinelJaval [/ James R. Cohn, CIH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division