NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 5 pages

Indoor air quality report, ATC, 2002

Machine-extracted title · confidence 28%

IAQ measurements collected March 13, 2002 at High School of Economics and Finance.

NYC-WTC_000384177–000384181
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 14, 2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance (M833) ATC Protect No. 15-19125-0291 of the twelve (12) instantaneous outdoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Indoor concentrations of relative humidity were within the applicable standards and guidelines. 3. Twenty-two (22) of the indoor measurements for temperature were above, twelve (12) were below and fifty-four (54) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions), 4. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading (1283 ppm) was measured in Room # 705 approximately at 1:36 PM with 43 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. 5. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the eight-eight (88) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. Two (2) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of the twelve (12) instantaneous outdoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.

CITY_2 IMCl 0 0_0 0 Cl 4 6 7 8 6 5 NYC-WTC_000384180

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000384180Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000402465

Indoor air quality measurements collected at the referenced school in March 2002.

Similar indexed content

NYC-WTC_000402524

Indoor air quality measurements collected March 19, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000404462

IAQ measurements at HS of Economics and Finance, April 8, 2002.

Similar indexed content

Compare copies and versions →