NYC-WTC_000384236
Indoor air quality measurements collected at HS Economics & Finance for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗IAQ measurements collected March 13, 2002 at High School of Economics and Finance.
NYC-WTC_000384177–000384181OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 14, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Protect No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 8:03 A.M. and concluded after 2:54 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 62.3 °F to 78.4 °F. Twenty-two (22) of the indoor measurements for temperature were above, twelve (12) were below and fifty-four (54) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 44.3 to 48.7 °F.
Relative Humidity
The relative humidity indoors ranged from 30,9 percent to 59.8 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 18.7 to 33.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 439 ppm to 1283 ppm. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 501 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1201 ppm (background level + 700 ppm). The highest reading (1482 ppm) was measured in Room # 705 approximately at 1:36 PM with 43 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were between 0 to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 2 to 4 ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 61 pg/m^ with an average 13 pg/m^- All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the eight-eight (88) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration ranged from 45 pg/m^ to 89 pg/m^ with an average of 59 pg/m^. Two (2) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All
CITY_21MC100_000467864 NYC-WTC_000384179
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000384236
Indoor air quality measurements collected at HS Economics & Finance for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402465
Indoor air quality measurements collected at the referenced school in March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402524
Indoor air quality measurements collected March 19, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384192
IAQ measurements collected March 14, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404462
IAQ measurements at HS of Economics and Finance, April 8, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402480
Indoor air quality measurements collected on March 14, 2002 for the specified school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179980
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219378
ATC Associates report on indoor air quality measurements collected at the High School of Economics and Finance on April 8, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259161
Indoor air quality data collection at Trinity Place site, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402495
Indoor air quality measurements collected on March 15, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259111
Indoor air quality measurements submitted to BOE for the High School of Economics and Finance, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402533
Indoor air quality measurements collected March 21, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000384207
Indoor air quality measurements at HS of Economics & Finance for BOE, March 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404467
IAQ measurements at 100 Trinity Place, performed April 9, 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404481
Report of IAQ measurements at High School of Economics and Finance (M833) for BOE in Apr 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383080
IAQ measurements conducted April 11, 2002 for BOE at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402480
Indoor air quality measurements collected on March 14, 2002 for the specified school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402542
Indoor air quality measurements collected March 25, 2002 at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000384236
Indoor air quality measurements collected at HS Economics & Finance for BOE program.
Similar indexed content
Indoor air quality measurements collected at the referenced school in March 2002.
Similar indexed content
Indoor air quality measurements collected March 19, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000384192
IAQ measurements collected March 14, 2002 at the referenced school.
Similar indexed content
IAQ measurements at HS of Economics and Finance, April 8, 2002.
Similar indexed content