Mr. Bernard P. Orlan March 14, 2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance (M833)___________________ ATC Project No. 15-19125-0291 of the twelve (12) instantaneous outdoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

Tl^OC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVO(/ concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debns; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Indoor concentrations of relative humidity were within the applicable standards and guidelines. 3. Twenty-two (22) of the indoor measurements for temperature were above, twelve (12) were below and fifty-four (54) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading (1283 ppm) was measured in Room # 705 approximately at 1:36 PM with 43 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. 5. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m- 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the eight-eight (88) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. Two (2) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of the twelve (12) instantaneous outdoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.

CONFIDENTIAL, CITY_21MC100_003462015 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259089

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259089Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259136

Indoor air quality measurements report for the High School of Economics and Finance, March 2002.

Similar indexed content

NYC-WTC_000179985

Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 21, 2002.

Similar indexed content

NYC-WTC_000259315

ATC summary of IAQ measurements conducted May 2, 2002 at 100 Trinity Place.

Similar indexed content

NYC-WTC_000259141

Indoor air quality measurements collected on March 20, 2002 for BOE.

Similar indexed content

Compare copies and versions →