machine-extracted · confidence unavailable · Check page ↗ATC IAQ measurements report for High School of Economics and Finance, 100 Trinity Place, 2002.
NYC-WTC_000402451–000402454OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orian March 13, 2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance fM833) ATC Project No. 15-19125-0291 of the twelve (12) instantaneous outdoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: o The interior of the building appeared clean and free of dust and debris; o The building was occupied at the time of the assessment; o No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Concentrations of relative humidity were within the applicable standards and guidelines. 3. Thirty-four (34) of the indoor measurements for temperature were below and forty-nine (49) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. Seven (7) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading (1482 ppm) was measured in Room # 705 approximately at 4:29 PM with 21 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. 5. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 qg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Two (2) of the eight-eight (88) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.
It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 336 or 212.
Sincerely, .4 TC^iSSOClA TES INC. Reviewed by: ■'1
Arnel Javal James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_002924185
NYC-WTC_000402454
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000384163
IAQ report covering measurements and signatures for school site.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402542
Indoor air quality measurements collected March 25, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000383080
IAQ measurements conducted April 11, 2002 for BOE at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384250
Chain-of-custody for potable water sampling at Trinity Place site, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396436
May 3, 2002 IAQ measurements for BOE at HSEF (M833).
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179976
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 12, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384125
Indoor air quality report for school, measurements and professional signatures.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402538
Indoor air quality measurements collected March 22, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384258
Chain-of-custody document for potable water samples collected at 104 East 25th Street.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384246
Indoor air quality measurements collected on March 22, 2002 at HS Economics & Finance.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404481
Report of IAQ measurements at High School of Economics and Finance (M833) for BOE in Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402546
Indoor air quality measurements collected March 26, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000384163
IAQ report covering measurements and signatures for school site.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384236
Indoor air quality measurements collected at HS Economics & Finance for BOE program.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402524
Indoor air quality measurements collected March 19, 2002 at the referenced school.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259136
Indoor air quality measurements report for the High School of Economics and Finance, March 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179976
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 12, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396436
May 3, 2002 IAQ measurements for BOE at HSEF (M833).
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000384163
IAQ report covering measurements and signatures for school site.
Similar indexed content
NYC-WTC_000402542
Indoor air quality measurements collected March 25, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000383080
IAQ measurements conducted April 11, 2002 for BOE at the referenced school.
Similar indexed content
NYC-WTC_000384250
Chain-of-custody for potable water sampling at Trinity Place site, March 2002.
Similar indexed content
May 3, 2002 IAQ measurements for BOE at HSEF (M833).
Similar indexed content