NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 6, 2002
Indoor Air Quality Assessment Page 4
H.S. of Economics and Finance (M833) 2yXLProiectNoa521912i4)291
were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and
children.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TyOCConcerUrqtion
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDING
Based on the real-time measurements, the following findings are presented:
1. Indoor concentrations of CO and TVOCs were below applicable standards and guidelines.
2. All the indoor measurements collected were within the range of 73 to 79°F (at 50 percent
relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season.
3. All the indoor measurements for relative humidity were bellow the ASHRAE recommended
range of 30 to 60 percent for occupant comfort.
4. Three (3) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
outdoor (background) CO2 concentration was 472 ppm. Therefore, the maximum acceptable
level of CO2 at this location was 1172 ppm (background level + 700 ppm). The highest
reading (1496 ppm) was measured in room #410 around 3:05 PM.
5. One (1) of the eighty-eight (88) indoor instantaneous measurements were above the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children. Seven (7)
outdoor instantaneous measurements were above the USEPA recommended concentration of 40
pg/m3 for sensitive individuals and children.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension 211
or 212.
Sincerely,
ATCASSOCL4 TES INC.
Re^wed by:
"^sad boddapaneni
Tames R. Cohn; CIH, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_002882083
NYC-WTC_000219873