NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan May 6, 2002
Indoor Air Quality Assessment Page 3
H.S. of Economics and Finance (M833) ATCPrpiectNpJ54912y:0291
Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of
eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are
found in the Attachment. Readings were collected between morning to evening. The results are
described below.
Temperature
Indoor dry bulb temperature measurements ranged from 69.5 °F to 76.2 °F. All the indoor
measurements collected were within the range of 73 to 79°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor
temperature measurements ranged from 62.0 °F to 68.5 °F.
Relative Humidity
The relative humidity indoors ranged from 19.2 percent to 29.2 percent. Ail the mdoor
measurements for relative humidity were bellow the ASHRAE recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity ranged from 18.1 to 20.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 386 ppm to 1496 ppm. Three (3) of the
indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended
maximum concentration of <700 ppm above the background level. The outdoor (background)
CO2 concentration was 472 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1172 ppm (background level + 700 ppm). The highest reading (1496 ppm) was
measured in room #410 around 3:05 PM. Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor
air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors was 0 ppm. These concentrations were below the
NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to
3 ppm.
Respirable Particulates (PM2,s)
Respirable particulate concentrations* indoors ranged between 0 pg/m^ to 51 pg/m^ with an
average 7 pg/m^- One (1) of the indoor measurements for respirable particulates was above the
NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or
less in aerodynamic diameter. One (1) of the eighty-eight (88) indoor instantaneous
measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive
individuals and children. The outdoor respirable particulate concentration ranged from 19 pg/m^
to 56 pg/m^ with an average of 40 pg/m^. All outdoor measurements for respirable particulates
were within the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5
micrometers or less in aerodynamic diameter. Seven (7) outdoor instantaneous measurements
CITY_21MC100_002882082