NYC Law Department release
Independent mirror · updated as the City releases more · v1.3.2
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

NYC-WTC_000219870

Label derived from the City's folder field. The City does not supply document titles.NYC-WTC_000219870–000219873
Page image
Scanned page image, NYC-WTC_000219872
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 6, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATCPrpiectNpJ54912y:0291 Real-Time Environmental Measurements

ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 69.5 °F to 76.2 °F. All the indoor measurements collected were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 62.0 °F to 68.5 °F.

Relative Humidity

The relative humidity indoors ranged from 19.2 percent to 29.2 percent. Ail the mdoor measurements for relative humidity were bellow the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 18.1 to 20.8 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 386 ppm to 1496 ppm. Three (3) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 472 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1172 ppm (background level + 700 ppm). The highest reading (1496 ppm) was measured in room #410 around 3:05 PM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors was 0 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.

Respirable Particulates (PM2,s)

Respirable particulate concentrations* indoors ranged between 0 pg/m^ to 51 pg/m^ with an average 7 pg/m^- One (1) of the indoor measurements for respirable particulates was above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. One (1) of the eighty-eight (88) indoor instantaneous measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 19 pg/m^ to 56 pg/m^ with an average of 40 pg/m^. All outdoor measurements for respirable particulates were within the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Seven (7) outdoor instantaneous measurements

CITY_21MC100_002882082

NYC-WTC_000219872

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000219872Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000179976

Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 12, 2002.

Similar indexed content

NYC-WTC_000180045

Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.

Similar indexed content

Compare copies and versions →