Mr. B ernard P. Ori an May 8, 2002 Indoo • Air Quality Assessment Page 3 H.S. cf Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real -Time Environmental Measurements
ATC ;ollected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are descrined below.
Temperature
Indoor dry bulb temperature measurements ranged from 71.1 °F to 85.9 °F. Thirty-six (36) of the indoor measurements collected were below and two (2) indoor measurements were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature measurements ranged from 71.2 °F to 80.1 °F.
R^latijeHumklir^
The relative humidity indoors ranged from 45.3 percent to 55.6 percent. All of the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percer t for occupant comfort. The outdoor relative humidity ranged from 48.0 to 55.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 426 ppm to 1261 ppm. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 493 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1 93 ppm (background level ■+■ 700 ppm). The highest reading (1261 ppm) was measured in room a 507 around 8:30 A.M. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primaiy source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NP^AQS/ASllRAE guideline of 9 ppm. The outdoor CO concentrations were also 1 ppm for all readings..
Respirable Particulates (PM2j)
Respirable pan.iculate concentrations* indoors ranged between 14 (ig/m^ to 25 jug/m^ with an average of 20 pg/m^- All of the indoor and outdoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Three (3) of the outdoor instantaneous measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.
CONFIDENTIAL, CITY_21MC100_003462494 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259360
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259425
Indoor air measurements collected May 20, 2002 for BOE IAQ program.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259344
ATC indoor air quality measurements conducted May 6, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259539
ATC indoor air quality measurements at the High School of Economics and Finance, June 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259507
ATC IAQ measurements report for June 11, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259145
Report of IAQ measurements at 100 Trinity Place for BOE program, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259204
ATC report of IAQ measurements collected April 19, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259200
Indoor air quality measurements taken April 18, 2002 for BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180015
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 9, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259330
Indoor air measurements collected May 3, 2002 for the BOE IAQ program.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259515
ATC IAQ measurements report for June 13, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259495
ATC IAQ measurements report for June 5, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180089
Report of indoor air quality measurements collected at the referenced school on June 14, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259401
ATC indoor air quality measurements collected May 14, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396531
Measurements collected May 14, 2002; BOE monitoring.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396559
ATC reports IAQ measurements collected May 16, 2002 at the school for BOE review.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259523
ATC IAQ measurements report for June 18, 2002 at the school.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396645
ATC IAQ measurements collected May 24, 2002 for IAQ assessment.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396715
ATC IAQ measurements collected June 17, 2002 as part of BOE monitoring.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air measurements collected May 20, 2002 for BOE IAQ program.
Similar indexed content
ATC indoor air quality measurements conducted May 6, 2002 for BOE.
Similar indexed content
NYC-WTC_000259539
ATC indoor air quality measurements at the High School of Economics and Finance, June 24, 2002.
Similar indexed content
ATC IAQ measurements report for June 11, 2002 at the school.
Similar indexed content
Report of IAQ measurements at 100 Trinity Place for BOE program, March 2002.
Similar indexed content