NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, High School of Economics and Finance, May 2002

Machine-extracted title · confidence 33%

ATC indoor air quality measurements collected May 14, 2002.

NYC-WTC_000259401–000259404
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 15, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements

ATC collected one hundred and three (103) sets of real-time environmental measurements consisting of ninety-one (91) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 71.2 °F to 80.8 °F. Seven (7) of the indoor measurements collected were below and fifteen (15) measurements were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 62.5 °F to 67.9 °F.

Relative Humidity

The relative humidity indoors ranged from 28.6 percent to 43.5 percent. Six (6) of the indoor measurements for relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 29.3 to 37.6 percent.

CafjwnDipxideConcen^tion

Carbon dioxide concentrations indoors ranged from 413 ppm to 1243 ppm. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 541 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1241 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 2 ppm for all readings, 'fhese concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were also 2 ppm for all collected readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 30 pg/m^ with an average of 16 pg/m^- All of the indoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 13 pg/m? to 44 pg/m3 with an average of 27 pg/m^-

CONFIDENTIAL, CITY_21MC100_003462568 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259403

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259403Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000396699

ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.

Similar indexed content

NYC-WTC_000396531

Measurements collected May 14, 2002; BOE monitoring.

Similar indexed content

NYC-WTC_000259507

ATC IAQ measurements report for June 11, 2002 at the school.

Similar indexed content

NYC-WTC_000396516

Indoor air quality measurements collected May 13, 2002 for BOE.

Similar indexed content

Compare copies and versions →