ATC IAQ measurements reported to BOE for the referenced school, May 2002.

NYC-WTC_000385004–000385007
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan May 22, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental measurements

ATC collected one hundred and six (106) sets of real-time environmental measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 67.1 °F to 80.1 °F. Forty-two (42) of the indoor measurements for temperature collected were below and six (6) indoor temperature measurements were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 60.6 °F to 67.4°F.

Relative Humidity

The relative humidity indoors ranged from 20.1 percent to 35.9 percent. Sixty-two (62) of the indoor measurements for relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 25.6 to 27.4 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 501 ppm to 1368 ppm. Six (6) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 571 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1271 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 to 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm for all collected readings.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 7 pg/m^ to 36 pg/m^ with an average of 14 pg/m^- None of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 32 pg/m^ to 52 pg/m^ with an average of 40 pg/m^ ■

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

C11Y_21MC100_002882210

NYC-WTC_000385006

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000385006Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000396645

ATC IAQ measurements collected May 24, 2002 for IAQ assessment.

Similar indexed content

NYC-WTC_000396723

ATC IAQ measurements collected June 19, 2002 under BOE IAQ program.

Similar indexed content

Compare copies and versions →