Mr. Bernard P. Orlan May 23, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred and six (106) sets of real-time environmental measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 64.9 °F to 80.1 °F. Thirty-nine (39) of the indoor measurements for temperature collected were below and five (5) indoor temperature measurements were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 56.8 °F to 68.3 °F.
Relative Humidity
The relative humidity indoors ranged from 24.3 percent to 39.7 percent. Sixteen (16) of the indoor measurements for relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 24.1 to 39.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 499 ppm to 1301 ppm. One (1) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 591 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1291 ppm (background level * 700 ppm). The highest reading was taken in room 605 at 12:15 PM with 29 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 to 2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 1 ppm for all collected readings.
Respirable Particulates (PM2J)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 18 pg/m^ with an average of 12 pg/m^- None of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or above the USEPA recommended concentration of 40 pg/m3 for sensitive individuals and children. The respirable concentrations outdoors ranged between 41 pg/m^ to 53 pg/m^ with an average of 45 pg/m^ ■
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
CITY_21MC100_002891544
NYC-WTC_000396622
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000396591
IAQ measurements collected May 20, 2002 at the referenced school for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396559
ATC reports IAQ measurements collected May 16, 2002 at the school for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384991
ATC indoor air quality measurements at the referenced school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396667
IAQ measurements collected May 30, 2002 for BOE IAQ program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396575
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259417
Indoor air quality measurements collected May 16, 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396675
IAQ data with TVOCs, CO, and particulates for Trinity Place site, Jun 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385071
ATC IAQ measurements collected on June 3, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180045
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259443
ATC report of IAQ measurements at High School of Economics and Finance, May 22, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259447
ATC report of IAQ measurements at the referenced school, May 23, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384975
ATC IAQ measurements at 100 Trinity Place (HS of Economics and Finance) for BOE in May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000385004
ATC IAQ measurements reported to BOE for the referenced school, May 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396667
IAQ measurements collected May 30, 2002 for BOE IAQ program.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396575
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259515
ATC IAQ measurements report for June 13, 2002 at the school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396645
ATC IAQ measurements collected May 24, 2002 for IAQ assessment.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000404586
IAQ report for High School of Economics and Finance (M833) dated May 1, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ measurements collected May 20, 2002 at the referenced school for BOE review.
Similar indexed content
ATC reports IAQ measurements collected May 16, 2002 at the school for BOE review.
Similar indexed content
ATC indoor air quality measurements at the referenced school, May 2002.
Similar indexed content
IAQ measurements collected May 30, 2002 for BOE IAQ program.
Similar indexed content
ATC IAQ measurements collected May 17, 2002 for BOE program on maintaining IAQ.
Similar indexed content