Mr. Bernard P. Orlan May 1,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 64.4 °F to 76.4 °F. Twenty-nine (29) measurements were below and fifty-nine (59) measurements were within the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 60.5 °F to 69.8 °F.
Relative Humidity
The relative humidity indoors ranged from 28.7 percent to 41.4 percent. Six (6) of the indoor measurements for relative humidity were below and eighty-two (82) measurement were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 23.5 to 37.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 433 ppm to 2785 ppm. Twenty-five (25) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 495 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1195 ppm (background level + 700 ppm). The highest reading (2785 ppm) was measured in Room #509 around 11:40 AM with 20 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 0 ppm to 2 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 8 pg/m^ to 63 pg/m^ with an average 25 pg/m^- All of the indoor measurements for respirable particulates were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Thirteen (13) of the indoor measurements and all twelve (12) of the outdoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 45 pg/m3 to 103 pg/m3 with an average of 64 pg/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
CITY_21MC100_002900428
NYC-WTC_000404588
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000384991
ATC indoor air quality measurements at the referenced school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259286
May 1, 2002 IAQ measurements for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396591
IAQ measurements collected May 20, 2002 at the referenced school for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396474
Indoor air quality measurements collected May 8, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396699
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396559
ATC reports IAQ measurements collected May 16, 2002 at the school for BOE review.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385071
ATC IAQ measurements collected on June 3, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396516
Indoor air quality measurements collected May 13, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396667
IAQ measurements collected May 30, 2002 for BOE IAQ program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259417
Indoor air quality measurements collected May 16, 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396620
IAQ measurements collected May 22, 2002 for BOE IAQ maintenance program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384900
May 9-10 IAQ measurements at the school, part of BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259286
May 1, 2002 IAQ measurements for BOE program.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396667
IAQ measurements collected May 30, 2002 for BOE IAQ program.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396620
IAQ measurements collected May 22, 2002 for BOE IAQ maintenance program.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384991
ATC indoor air quality measurements at the referenced school, May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180045
Letter from ATC Associates reporting indoor air quality measurements collected at a school on May 15, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385004
ATC IAQ measurements reported to BOE for the referenced school, May 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC indoor air quality measurements at the referenced school, May 2002.
Similar indexed content
May 1, 2002 IAQ measurements for BOE program.
Similar indexed content
IAQ measurements collected May 20, 2002 at the referenced school for BOE review.
Similar indexed content
Indoor air quality measurements collected May 8, 2002 for BOE.
Similar indexed content
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
Similar indexed content