Mr. Bernard P. Orlan May 21,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833 )________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements

ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 63.1 °F to 80.1 °F. Twenty-two (22) of the indoor measurements for temperature collected were below and twenty-one (21) indoor temperature measurements were above the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 57.9 °F to 69.6°F.

Relative Humidity

The relative humidity indoors ranged from 17.6 percent to 34.5 percent. Sixty-six (66) of the indoor measurements for relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 16.0 to 21.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 584 ppm to 1460 ppm. Sixteen (16) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 502 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1202 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentralion

Carbon monoxide concentrations indoors ranged from 0 to 2 ppm for all readings. ITiese concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations also ranged from 0 ppm to 2 ppm for all readings.

Respirable Particulates (PM2,3)

Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 75 pg/m^ with an average of 10 pg/m^- Two (2) of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Three (3) of the indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children, 'fhc respirable concentrations outdoors ranged between 18 pg/m^ to 53 pg/m^ with an average of 37 pg/m^ •

* The measurements made during this assessment were instantaneous readings, the NPAAQS is

CITY_21MC100_002882256

NYC-WTC_000384993

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000384993Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000396591

IAQ measurements collected May 20, 2002 at the referenced school for BOE review.

Similar indexed content

NYC-WTC_000396620

IAQ measurements collected May 22, 2002 for BOE IAQ maintenance program.

Similar indexed content

NYC-WTC_000396516

Indoor air quality measurements collected May 13, 2002 for BOE.

Similar indexed content

NYC-WTC_000396723

ATC IAQ measurements collected June 19, 2002 under BOE IAQ program.

Similar indexed content

Compare copies and versions →