IAQ report, High School of Economics and Finance, June 2002

Machine-extracted title · confidence 28%

ATC IAQ measurements report for June 17, 2002 at the school.

NYC-WTC_000259519–000259522
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 18,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)_______ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements

ATC collected one hundred and six (106) sets of real-time environmental measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 73.0 °F to 80.2 °F. Twenty-six (26) of the indoor measurements for temperature were above the range of 73 °F to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 74.5 °F to 77.0 °F.

Relative Humidity

The relative humidity indoors ranged from 41.8 percent to 50.8 percent. All of the indoor measurements for relative humidity were within ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 46.1 to 50.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 469 ppm to 888 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 484 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1184 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 2 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 5 pg/m3 to 35 pg/m^ with an average of 12 pg/m^. None of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 45 pg/m^ to 60 pg/m3 with an average of 50 pg/m^ •

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CONFIDENTIAL, CITY_2IMCl00_003462901 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259521

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259521Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259523

ATC IAQ measurements report for June 18, 2002 at the school.

Similar indexed content

NYC-WTC_000259531

ATC IAQ measurements report for June 20, 2002 at the school.

Similar indexed content

NYC-WTC_000396723

ATC IAQ measurements collected June 19, 2002 under BOE IAQ program.

Similar indexed content

NYC-WTC_000259286

May 1, 2002 IAQ measurements for BOE program.

Similar indexed content

Compare copies and versions →