Mr. Bernard P. Orlan June 26,2002
Indoor Air Quality Assessment Page 3
H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291
Real-Time Environmental Measurements
ATC collected one hundred and six (106) sets of real-time environmental measurements
consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data
sheets are found in the Attachment. Readings were collected in the morning and in the evening.
The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 75.1 °F to 83.6 °F. Fifty (50) of the
indoor measurements for temperature were above the range of 73 °F to 79°F (at 50 percent
relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The
outdoor temperature measurements ranged from 82.2 °F to 86.1 °F.
Relative Humidity
The relative humidity indoors ranged from 38.0 percent to 52.1 percent. All of the indoor
measurements for relative humidity were within ASHRAE recommended range of 30 to 60
percent for occupant comfort. The outdoor relative humidity ranged from 47.8 to 53.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 512 ppm to 836 ppm. All of the indoor
measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentration was 601 ppm. Therefore, the maximum acceptable level of CO2 at this location
was 1301 ppm (background level + 700 ppm). Levels above the recommended maximum do not
indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor
air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations
were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged
from 0 ppm to 2 ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 55 pg/m^ with an
average of 14 pg/m^- None of the indoor measurements for respirable particulates were above
the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers
or less in aerodynamic diameter. Five (5) of the indoor measurements were above the USEPA
recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable
concentration outdoors ranged between 26 pg/m^ to 71 pg/m^ with an average of 54 pg/m^ •
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.