Indoor air quality report, HSof Economics and Finance, Jun 2002

Machine-extracted title · confidence 28%

ATC indoor air quality measurements at the referenced school, June 25, 2002.

NYC-WTC_000259543–000259546
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 26,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements

ATC collected one hundred and six (106) sets of real-time environmental measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected in the morning and in the evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 75.1 °F to 83.6 °F. Fifty (50) of the indoor measurements for temperature were above the range of 73 °F to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 82.2 °F to 86.1 °F.

Relative Humidity

The relative humidity indoors ranged from 38.0 percent to 52.1 percent. All of the indoor measurements for relative humidity were within ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 47.8 to 53.6 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 512 ppm to 836 ppm. All of the indoor measurements for CO2 were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 601 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1301 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 0 ppm to 2 ppm.

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 55 pg/m^ with an average of 14 pg/m^- None of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Five (5) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentration outdoors ranged between 26 pg/m^ to 71 pg/m^ with an average of 54 pg/m^ •

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CONFIDENTIAL, CITY_21MC100_003462997 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259545

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259545Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000223596

Report of indoor air quality measurements collected at the High School of Economics and Finance on June 25, 2002.

Similar indexed content

NYC-WTC_000396735

ATC collected IAQ data for June 26, 2002 at the school, per BOE request.

Similar indexed content

NYC-WTC_000223592

Report of indoor air quality measurements collected at the High School of Economics and Finance on June 24, 2002.

Similar indexed content

NYC-WTC_000259523

ATC IAQ measurements report for June 18, 2002 at the school.

Similar indexed content

Compare copies and versions →