Mr. liemard P. Orlan June 26, 2002
Indoor Air Quality Assessment Page 2
H.S. of Economics and fiance (M833) ATC Project No. 15-19125-0291
The results of the sampling represent conditions found on the dates of the survey and may not
represent conditions found at other times. The information presented in this report should be
used by the BOE as a guide to assess the need for further improvements in current indoor air
quality control activities.
FAAIATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings,
such as offices and schools. For the real-time data collected, ATC uses the commonly accepted
guide ines cited in the following publications:
Ventilation far Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal Environmental Conditions far Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industi'ial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation.
Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality
will be achieved at all times.
TABLE 1
TAROET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL
ORGANIZE ION
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO:) above background level
Carbon Monoxide 9 ppm ASHRAE 62 (adopted from
(CO) USEPA NPAAQS)
Resp table 65 micrograms per cubic meter USEPA NPAAQS
Particulates (PM2.5) of air (pg/m3) 24-hour average
40 pg/m^ 24-hour average USEPA - Recommendation for
children / sensitive individuals
Temperature Summer: 73-79°F at 50% RH ASHRAE 55
Winter: 68-75°F at 50% RH
Relative Humidity 30 - 60 % ASHRAE 55
Total Volatile
Orga: tic Compounds 1 ppm AIHA
(TVOC)
L’SEP/ = United States Environmental Protection Agency
NPAA()S = National Primary Ambient-Air Quality Standard
AIHA == American Industrial Hygiene Association
CONFIDENTIAL, CITY_21MC100_0 03462996
SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008